Journal of the Magnetics Society of Japan
Online ISSN : 1880-4004
Print ISSN : 0285-0192
ISSN-L : 0285-0192
Power Magnetics
A New Bridge-Type Transformer Using a Three-Leg Core and Its Application to a Removable 5th-Harmonic Voltage Transformer
S. OkanumaK. TerauchiA. HayasakaO. Ichinokura
Author information
JOURNAL OPEN ACCESS

1999 Volume 23 Issue 4_2 Pages 1493-1496

Details
Abstract
In a previous paper, we proposed a reactor circuit comprising a combination of reactors, single-phase transformers, and resistances. The reactor circuit can remove the 5th-harmonic voltages from its three-phase output voltage. In this paper, we present a new bridge-type three-phase transformer using a three-leg core and a E-form core. Both the line and phase voltages of the three-phase voltage source are applied to the transformer windings. The 5th-harmonic component of the output voltage decreases, because the 5th-harmonic component due to the line voltage and that due to the phase voltage cancel each other out. We describe the operating principle of the bridge-type transformer and its application to a removable 5th-harmonic voltage transformer.
Content from these authors
© 1999 by The Magnetics Society of Japan
Previous article Next article
feedback