Abstract
In order to evaluate initial permeability of large concrete structure, hollow cylindrical reinforced concrete structure, having 6 m in outer diameter, 6 m in height, 1 m in thickness, had been tested by means of 0.25 MPa of outside water pressure. As the results, although surface cracking and partial separation of joint had been observed at the inner side, no water permeation through concrete could be happened even after 5.5 years. After this test, concrete core specimen showed less water penetration within the depth of concrete cover of reinforcement. Thus it was verified that this concrete structure had very high water-tightness, and that the initial average water permeability was estimated to be about 1.6×10-12 m/s.