Abstract
In case of that column diameter is restricted by the narrow construction space, Concrete filled steel tube column is used. Authors developed new arrangement of bars that the range of longitudinal reinforcement ratio is from 14.8% to 24.7% and the longitudinal reinforcements are reinforced by spiral reinforcement. For the confirmation of the damage form and the deformation performance of the column with new bar arrangement at the earthquake, static reversal cyclic loading test was carried out. The parameters are longitudinal reinforcement ratio, shear span ratio and strength ratio. As the result, the damage form showed different trends due to longitudinal reinforcement ratio, shear span ratio and flexural strength and shear strength ratio. And specimens with the new bar arrangement had a good ductility with rotation angle of the column more than 1/10 and no rapid decline of strength. And, it is possible to evaluate ultimate bending capacity by considering the damage situation at maximum load.