2022 Volume 78 Issue 2 Pages I_175-I_180
Ordinally, for corrosion protection in marine steel structures, cathodic protection methods is applied to M.L.W.L. or less, and coating protection methods is applied to L.W.L. -1.0m or more. Therefore, we considered to expand the effective range of cathodic protection in under-seawater to the coating protection area by applied high-conductivity mortar mixed with carbon as a covering material. it can reduce the resistance to 1/100 compared to ordinary concrete and confirmed that it can be protected with suppling 1mA/m2 or more in underwater environment and 100 mA/m2 or more in dry environment as corrosion protection current. Sufficient corrosion protection performance was confirmed at a range of L.W.L. +235 cm or less from result of 3.5 years-exposure test in marine environment.