Abstract
A perfobond strip is generally used as the shear connector in the various steel-concrete hybrid structures and a few design formulas for evaluating the shear resistance of the perfobond strip are proposed. However, these design formulas are not always applicable to the one employed in the steel-concrete rigid frame bridge, since the formulas are established based on the standard push-out specimen for the stud shear connector in which some cracks may occur in the concrete block of the specimen during the test. In this paper, the shear resistance of the perfobond strip are examined experimentally by employing the simple push-out specimen different from the standard one for the stud shear connector. As a result, the design formula is proposed for evaluating the shear resistance of the perfobond strip taking into account the proportion of the concrete block as well as the perforation size and the concrete compressive strength.