Bulletin of JSME
Online ISSN : 1881-1426
Print ISSN : 0021-3764
Kinetic Behavior of Mono-tube-boilers
Toshiro TERANO
Author information
JOURNAL FREE ACCESS

1960 Volume 3 Issue 12 Pages 540-546

Details
Abstract
The kinetic behavior of a mono-tube-boiler is very important for its control. Since the controlled variables of a boiler (pressure, temperature) are the complicated functions of enthalpy and distributed along the tube length, the kinetic analysis is not easy. In this paper, the author analyses it, supposing that the temperature is distributed but the pressure is lumped in the tube. The results are illustrated by a numerical example which represents the transient response for the stepwise change of fuel, feed-water and steam demand. He also applies them to the evaluation of the automatic control systems for mono-tube-boiler.
Content from these authors
© The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top