JSME International Journal Series B Fluids and Thermal Engineering
Online ISSN : 1347-5371
Print ISSN : 1340-8054
ISSN-L : 1340-8054
New Tube Arrangement of Condenser for Power Stations
Kenji SATOAkihiro TANIGUCHITakafumi KAMADARyoji YOSHIMURAYoshio MOCHIDA
Author information
JOURNAL FREE ACCESS

1998 Volume 41 Issue 3 Pages 752-758

Details
Abstract

Steam pressure loss in a tube bundle significantly influences condenser performance. Based on this fact, a new tube arrangement will be developed. The analytical study shows the advantage of this improvement : up to 20% higher heat transfer performance than from our former design(1). The method applied to estimate performance is a steam flow analysis using the finite volume method. To confirm the analytical results, hydraulic analogue tests with water are carried out. This new type condenser will be operated in power stations in the near future.

Content from these authors
© The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top