The Proceedings of the Symposium on Environmental Engineering
Online ISSN : 2424-2969
2006.16
Session ID : 416
Conference information
416 Energy Evaluation for Air Conditioning System Combined with Ventilation
Seiji INOUEMakoto SAITOHirokuni SUZUKI
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Simulation models of three types of air conditioning system combined with ventilation have been developed. The compared systems are as follows: (A) Duct type ventilation and air conditioner, (B) Duct type ventilation and air conditioner which inhale indoor air mixed with supply air (outdoor air), (C) Total heat exchange ventilation system and air conditioner. We calculated total energy consumption and indoor humidity in order to evaluate the effects of difference of ventilating system under various combinations of outdoor air temperature and humidity. As a result, we clarified that the annual energy consumption of system (B) decreases 3.4% compared with that of system (A), because the air conditioner operates efficiently by the indoor air mixed with the supply air. And we also clarified that the annual energy consumption of system (C) decreases 9.1% compared with that of system (A), because the air conditioning load decreases by the total heat exchanger of the ventilator.
Content from these authors
© 2006 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top