The Proceedings of the Symposium on Environmental Engineering
Online ISSN : 2424-2969
2006.16
Session ID : 423
Conference information
423 Improvement of thermal enviroment at Shinkansen train base by water atomization techonology : Influence of the temperature change on the quantity of water atomization
Seiji UCHIYAMAKazuaki IIJIMAKoji SUZUKIMakoto TSUJIMOTO
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
The purpose of this study is to analyze the effect of cooling by the water atomization in the Shinkansen train base. The temperature of the train base which vehicle is cleaned and is inspected exceeds 40℃ in summer. We established the water atomization in a part of the Shinkansen train base and experimented that changing the quantity of water to grasp the characteristic of the system. The temperature descent by latent heat of water mist was 5℃〜6℃ in favorable term.
Content from these authors
© 2006 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top