Abstract
In the present study, for the efficiency improvement of the centrifugal compressor for the turbo chiller in the part load region, the flow control device that had variable vane in the middle steps of the centrifugal compressor for the turbo chiller was developed. It was confirmed from the numerical simulation and experiment that the stall of the second stage impeller was suppressed and that higher efficiency was obtained in the part load region.