The Proceedings of the Fluids engineering conference
Online ISSN : 2424-2896
2016
Session ID : 0920
Conference information

Study on Diameter of Centrifugal Fan in Consideration of Heat Exchanger in 4-Way Cassette Type Indoor Unit of Packaged Air Conditioner
Daiwa SATOH[in Japanese][in Japanese][in Japanese][in Japanese]
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract

Air conditioners designed for an energy saving are required in a market. Improvement of a fan efficiency and uniformization of a velocity distribution in heat exchanger are necessary for improvement of a performance for energy saving. The velocity distribution and pressure-loss of heat exchanger and shaft power of the centrifugal fan were evaluated with Computational Fluid Dynamics (CFD). An appropriate diameter of the fan was determined by the result of the evaluation. Reducing the diameter to a certain value reduced the shaft power by approximately 4 % compared with a basic diameter. However, further reducing the diameter increase the shaft power in approximately 6 % compared with a basic diameter. These were caused by the change of the fan efficiency and the velocity distribution. In particular, we found the velocity distribution was related with the outlet height of the fan and a distance between the fan and the heat exchanger.

Content from these authors
© 2016 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top