The Proceedings of the International Conference on Power Engineering (ICOPE)
Online ISSN : 2424-2942
2009.3
Session ID : C305
Conference information
C305 ANALYSIS OF PERFORMANCE EFFECT OF HEAT SOURCE TEMPERATURE ON SILICA GEL-WATER ADSORPTION CHILLER(Heat Pump-2)
Xinling MAXinli WEIXiangrui MENCYao YAO
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Through experimental research of the performance effect about the heat source temperature to silica gel-water adsorption chiller, the results obtained show that with temperature increasing refrigerating output will grow, but increment rate is variational; and when the heat source temperature rises, the variety of COP is a wave curve, so COP value comes into being two wave crests and two troughs. With further studies on the microstructure and shape of silica gel, the investigation proves that the micropore of silica gel is mostly "inkbottle" shape, and the distribution of micropore diameter is well-regulated. The results show the adsorption-desorption hysteresis should be sufficiently taken into account when designing or appraising the silica gel-water adsorption chiller. It is also indicated that the micropore diameter of silica gel would match with heat source temperature when designing the experiment.
Content from these authors
© 2009 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top