B114 Application of inlet fogger Cooling System for Economical Power Boosting of Gas Turbine
Tatsuro UCHIDAFumio OOTOMOHidenori FUKUTAKEMasao ITOH
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
This paper describes a gas turbine inlet air cooling system using high pressure spray nozzle. Thermal characteristics and fluid properties were studied by performing the wind tunnel test that simulated an actual gas turbine intake cooling duct part. A result of examining the cooling performance due to differences in the inlet relative humidity 30〜50%RH, the cooling performance was the same. Furthermore, as a result of investigating the cooling performance due to the difference in a spray nozzle number, in one case, it became clear from 33 ℃ that it is possible for 28 ℃ to cool ,and in three case, it became clear from 33 ℃ that it is possible for 23 ℃ to cool. The result of obtaining with the relative humidity and temperature sensor was plotted on the psychrometric chart and the air humidifying cooling process of an actual gas turbine inlet duct part was clarified.