Performance of three-bed two-stage adsorption refrigerator operated with hot water of 60 degrees Celsius
Nobuya TakahashiMasayuki NakayamaAtsushi Akisawa
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract

The objective of this study is to examine proposed 2 stage adsorption refrigeration cycle consisting of 3 beds experimentally with hot water of 60 degC and cooling water of 30 degC. Low pressure side is running in the same way as conventional 2 stage cycle while high pressure side is operated twice as quickly as the low pressure cycle. It was confirmed that it worked with such a low grade driving heat source and there existed optimal cycle time to maximize the cooling capacity of the proposed cycle. The new operation with 4 times higher frequent cycle of the high pressure side was also examined, which actually worked and resulted in 19% improvement in terms of cooling capacity.