The Proceedings of the Thermal Engineering Conference
Online ISSN : 2424-290X
2011
Session ID : D125
Conference information
D125 Thermal performance enhancement and high-functionalization of heat pipes
Mayumi OUCHIYoshiyuki ABETakuro HAYASHIMiyoshi YOKURA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Two sizes of plate-type heat pipes were produced experimentally by diffusion bonding of two copper thin plates. Thermal performances of these plate-type heat pipes were examined by liquid cooling of condensation section. For large-scaled plate-type heat pipe which 3.8mm in thickness, 40mm in width, and 375mm in length, thermal resistance of 0.06K/W at maximum heat transport ratio of 250W was obtained in the bottom heat condition. Verification tests of cooling for CPU in server with these plate-type heat pipes were also carried out using real server, and CPU case temperatures were kept lower than 60℃ for both heat pipes.
Content from these authors
© 2011 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top