The Proceedings of the Thermal Engineering Conference
Online ISSN : 2424-290X
2014
Session ID : A113
Conference information
A113 Heat exchange performance in cooling mode of ground source heat pumps that use the direct expansion method
S. IshiguroT. TakedaD. YokoyamaD. TanakaS. FunataniK. Ichimiya
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
This paper describes the performance of GSHP (Ground Source Heat Pump) system that uses the direct expansion method. In the experimental apparatus, a borehole is 30 m in depth and R410A is used as a refrigerant. The ground source heat pump was operated continuously for 48 hours with the cooling mode. Temperature and pressure of the refrigerant were measured at 5 positions. Air temperature at the entrance and exit of an indoor unit were also measured. As a result of the experiment, the coefficient of performance (COP) of the GSHP became 12 when the set value of the room temperature is 27℃.
Content from these authors
© 2014 The Japan Society of Mechanical Engineers