The Proceedings of the Thermal Engineering Conference
Online ISSN : 2424-290X
2023
Session ID : B111
Conference information

Air Conditioning Performance of Ground Source Heat Pump Using Residential Steel Pipe Pile
*Yukito HoshiTetsuaki Takeda
Author information
CONFERENCE PROCEEDINGS RESTRICTED ACCESS

Details
Abstract

The purpose of this study is to investigate a heat exchange performance of a direct expansion type heat pump when an underground heat exchanger is inserted into a steel pipe pile. The underground heat exchanger is a U-shaped pipe with one copper pipe (outer diameter 4.0 mm, wall thickness 0.8 mm, length 10 m) and two copper pipes (same standard as one side) connected at the bottom. 12 underground heat exchangers are used, and 1.8 kg of R32 is used as the refrigerant. As a result of the experiment, the average coefficient of performance(COP) was 6.7 at the cooling set temperature of 25℃. It became 5.7 at the cooling set temperature of 27℃.

Content from these authors
© 2023 The Japan Society of Mechanical Engineers
Previous article Next article
feedback
Top