Thermal Responsiveness of Fusible Sprinkler and Its Actuation below a Confined Ceiling
Yuji HASEMIShinji SAKO
Author information
JOURNAL FREE ACCESS

1988 Volume 38 Issue 1 Pages 1-10

Details
Abstract

In order to improve the predictability of sprinkler response time for a confined ceiling, thermal properties of fusible sprinkler and environment of sprinklers below a confined ceiling during fire are discussed. A method of estimating the heat loss from a fusible link of the sprinkler fitting and the response of the link to external radiation is proposed. Measurements of temperature, velocity, radiation, and sprinkler response time below a ceiling are made in a 11.1 m × 8.1 m confined enclosure. The measured temperature and velocity are found to be close to previous theory for an unconfined ceiling if a correction for the existence of smoke layer is applied. Finally measured sprinkler response time is compared with calculation based on measured temperature, velocity and radiation history. The result shows the significance of radiation from the fire source in the determination of sprinkler response times.