Experimental Study on Air Leakage between Smoke Exhaust Opening and Duct
Takahiro MIURATatsuo AKIYAMAYoshitake NEMOTOToshiyuki MURAKAMIMasaki SENBOKUYAShigehiro IKEDAKazuhiro KIMURA
Author information
JOURNAL FREE ACCESS

2018 Volume 43 Issue 255 Pages 53-58

Details
Abstract

Smoke exhaust fans are selected considering the air leakage of the smoke exhaust system, because the gauge pressure in the system is very low. Air leakage occurs in various parts. The clearance between the smoke exhaust opening and the duct is the leakiest part in the system. In this study, experiments were conducted to clarify the air leakage rate between the smoke exhaust opening and duct at an arbitrary clearance with a hermetic sealing method. The air leakage rate was measured for three clearances with four sealing methods. The results showed that the air leakage rate for unsealed cases can be computed by using an orifice flow model. Air-leakage-rate equations for the sealed cases were obtained from the experimental values.

Content from these authors
© 2018, The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan
Previous article Next article