Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-0486
Print ISSN : 0385-275X
ISSN-L : 0385-275X
Scientific Paper
Development of Open-type Adsorption Thermal Storage Heat Pump System Applying HAS-Clay
Part 5-Demonstration Test of Off-line Heat Transport System
Haruyuki KAMATAYoshiaki KAWAKAMIKazumasa YAMAUCHIMasataka IMORIHiroyuki NAWASatoru MATSUDAMasaya SUZUKIHidetaka MIYAHARAAtsushi SATOMasayuki TANINO
Author information
JOURNAL FREE ACCESS

2022 Volume 47 Issue 301 Pages 9-16

Details
Abstract

We developed an open-cycle type adsorbent thermal storage system with HAS-Clay to utilize low-temperature waste heat. The demonstration tests were performed no a stationary type and an offline heat transportation type after the development of systems and materials, such as the durability of HAS-Clay. In the offline heat transportation type, the thermal storage tank charged in the co-generation system was transported by the tractor-trailer and used to heat up water and air in a swimming center. It was evaluated as an absorption-based heat storage system through three seasons: summer, interphase, and winter. The test data indicated a regenerating efficiency of 90% or more. The charge/discharge characteristics of the system were also evaluated. In addition, by comparing the test data with the numerical analysis model on the charge/discharge operations, it was confirmed that the numerical analysis model can be used as a design tool.

Content from these authors
© 2022, The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan
Previous article Next article
feedback
Top