2023 Volume 48 Issue 310 Pages 39-45
We studied the use of a combined exhaust auxiliary device that blows air from the inner side of a concave blow outlet, to converge and lift air, while sucking the surrounding air to improve the capture performance of a canopy-type exhaust hood, which is affected by turbulent airflow as the buoyancy lift effect caused by a temperature difference can be unexpected. The effects of exhaust auxiliary device were investigated experimentally and using computational fluid dynamics (CFD) analysis for a ventilation facility configured to generate carbon dioxide in a space where the airflow is blown in at 1 m/s, and to capture carbon dioxide in the exhaust hood located 1m above. The results showed that the exhaust auxiliary device significantly improved the hood exhaust capture efficiency (from 24.5% to 93.7% in the experiment, and from 28.1% to 89.1% in the CFD analysis) and confirmed.