Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2004.1
Session ID : F-13
Conference information
F-13 Coincidence Measurement of Ventilation Rate and VOCs : Development of Simultaneous Sampling and Analysis Method for 4 Tracer Gases and Applying to Ventilation Measurement
Miyuki NOGUCHIKazukiyo KUMAGAIHiroshi YOSHINOMinoru FUJIIYumiko OKUIZUMIKuniaki MIHARAYukio YANAGISAWA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Ventilation is the most effective procedure to reduce indoor air pollutant. Volatile organic compounds (VOCs), which cause health related symptoms, are often detected in the indoor environment. The way of ventilation should be decided depending on the VOCs level. VOCs level and air exchange rate are usually measured individually. This study will propose a simple method to measure both the ventilation rate by perflourocarbon tracer gas technique (PFT) and VOCs concentration at once by using a single sampler. A glass vial with a diffusion cap on top was selected as a doser, filled with perfluorocarbon (PFC). A thermal desorption (TD) tube packed with carbon adsorbent was used as a sampler. TD and a gas chromatograph - mass spectrometer (GC-MS) was employed for injection and analysis, respectively. Selected analysis conditions enable to separate VOCs as well as PFC. According to this method, low cost, less complex and shorter time for analysis were to be possible.
Content from these authors
© 2004 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan
Previous article Next article
feedback
Top