A-6 Comprehensive Verification Method for a Rainwater Recycling System that enables the Refurbishment of Urban Building Stocks : (Part 2 Inspections of the propriety of rain reuse system design and the stability of water quality)
Akihiro NAGANOMasayuki OOTSUKAKeiko NOJIMasanobu YUZAWAKouichi SHINMURA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
A 36-years-old laboratory refurbished at 2005. A new rain recycling system was installed and operated these 1.5 years. In 2006, 1700mm rain was felled at Yokohama area. 80% of rain was collected and used in the system. The quantity of rain water was about 400 m3 from 300 m2 roof and the quality of treated rain water was kept safety level in coliform, egionella content and other factors.