A-18 An Experimental Study on the Energy Consumption Performance of Pipe Freeze Prevention Heaters : Part 1; Basic Performance of Pipe Freeze Prevention Heaters
Satoshi SUDOShinya MOURIHitoshi AKAIYorimasa IKIMasataka YOKOYAMA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
In order to understand the basic performance of pipe freeze prevention heaters, the experimental study was carried out. Results of this study are as follows 1) The self-control type heaters run hot at ambient temperature 30-40 degrees Celsius. 2) The self-control heaters become 10-20 degrees higher than the ambient temperature. When a switch was not cut, it may become a problem. 3) When ambient temperature is more than 5-7 degrees Celsius, electric current of the thermostat type heaters stop. 4) About energy consumption, the thermostat type heaters are more effective than the self-control type heaters.