Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2009.3
Session ID : F-64
Conference information
F-64 A Study on the Indoor Air Pollution Caused by Unvented Combustion Appliances
Atsuo NOZAKIYuki YAMASHITAYasunori NARITA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Unvented combustion appliances discharge various contaminants indoors. In earlier studies concentration of CO, NO_x hydrocarbosn, aldehydes, and VOCs discharged from each of unvented combustion appliances was measured in a large scale chamber. The present study investigated the discharge of these substances and ammonia in a residential environment by performing the survey in residence.The results showed that aldehydes concentration of the unvented combustion appliances are in the range of 1.64 to 30.1 [μg/m^3], and a TVOC concentration maximum of 505[μg/m^3]The serious indoor air pollution is caused by use of the unvented combustion appliance.
Content from these authors
© 2009 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan