Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2010.2
Session ID : F-45
Conference information
F-45 Field Survey of Indoor Environment of National Museum of Western Art forDeveloping of Retrofit Scheme : Part II : Study on Indoor Environment Using CFD
Takeshi OGASWARATakashi KURABUCHIKazunori HOSONOHajime YOSHINOHiroshi OCHIAI
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Based on the observation, we examined an indoor airflow and detailed distribution of age of air at main building of the National Museum of Western Art. Also from the view of the recovery of the authenticity which is important world heritage registration, we predicted the event that glass board partitions which didn't exist the original design were to be removed by using CFD. We confirmed actual measurements of air age distribution and the reproducibility of CFD analysis results in the current condition. And if the partition were to be reverted, it is fear that outdoor air come in the 19th century hall.
Content from these authors
© 2010 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan
Previous article Next article
feedback
Top