Session ID : I-64
Conference information
I-64 A study of ventilation system for apartment buildings : Part 1) Field measurement of Air-Flow Rate Deterioration of Ventilation Opening
Hiroshi KIMURAYoshifusa Nishimura
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Indoor negative pressure by simultaneous use of exhaust fans causes such problems as increase of power needed for opening entrance door. In order to evaluate air-flow rate deterioration of ventilating openings in continuous ventilation, field measurement was conducted in apartment buildings for three months. The result showed that air-flow rate of ventilation filters decreased 3-8% during the period. Also, their dust removal performance remained throughout the period, and its air-flow rate was estimated to decrease around 5-15% in half year.
Content from these authors
© 2010 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan