Analytical study on shear-load capacity of RC caisson foundation side wall considering ground reaction
Yuki NakataJunichi AbeTomoya MasudaTakashi MiuraTakayuki TosakiMami NakamuraTaisuke SanagawaKen WatanabeToshiya Tadokoro
Author information
JOURNAL FREE ACCESS

2023 Volume 69A Pages 861-870

Details
Abstract

When the shear-load capacity of a side wall of RC caisson foundations is evaluated, the experimentally derived calculation formula for beams is currently usually applied. However, since a caisson foundation is subjected to the ground reaction force, the shear-load capacity of such structure may be affected by the difference in the supporting condition. In this study, the shear-load capacity of the side wall was evaluated by the non-linear finite element analysis, which can more realistically reflect such conditions. As a result, it was found that the side wall had a larger capacity and avoided shear failure. This means that it is desirable to rely on the non-linear finite element analysis for evaluation of the shear-load capacity of such underground structures as caisson foundations.