The Effect of Subcooling on the Flow and Heat Transfer Characteristics in a Two-Phase Loop Thermosyphon
Hideaki IMURAKazuhiro TAKESHITAKyoji DOIKen-ichi NODA
Author information
JOURNAL FREE ACCESS

1994 Volume 11 Issue 2 Pages 209-218

Details
Abstract
A two-phase loop thermosyphon is used as a heat transfer device in an energy-saving heat transportation system and so forth, because it transports thermal energy without any external power supply such as a pump under a body force field. We previously performed a fundamental study on the flow and heat transfer characteristics in a two-phase loop thermosyphon installed with a single heated tube evaporator both experimentally and theoretically which was made under the condition of near saturation temperature of liquid in a reservoir. In the present study, the effects of liquid subcooling and the heat input on the circulation mass flow rates, pressure and temperature distributions, and heat transfer coefficients in the evaporator were examined experimentally using water, ethanol, benzene and Freon 113 as the working fluids. On the other hand, the circulation mass flow rates, pressure and temperature distributions were theoretically calculated and compared with the experimental results.