Abstract
Slurry ice system is desirable as cold heat source for air conditioning, because it requires less conveyance power or less pipe size. On the other hand, recently absorption refrigerator is reevaluated because it can utilize various types of waste heat and it does not use fluorocarbon refrigerant. But it had been regarded to be difficult to make ice by absorption refrigerator because the refrigerant is water. However making slurry ice is possible, of cource, if the slurry ice generated by partial freezing of water is continuously taken away from the evaporator. This method was certified experimentally with a bench scale model. For ice making continuously, ice had not to be frozen stiff at water surface or inside wall of the evaporator. Then refrigerant water in the evaporator was raised swirl flow. And inside wall of the evaporator was finished by water repellent coating, and heated from outside wall. This slurry ice was adaptable to hydraulic transportation, because ice was needle crystal with about 5 mm length and ice temperature was 0°C.