1999 Volume 16 Issue 3 Pages 221-228
Applying actual cooling tower water analyses together with air pollution and meteorological records to the theoretical equation calculating M-alkalinity of cooling tower water which is formulated in consideration of air pollution, capture efficiencies of typical air-conditioning cooling tower for each air pollutant have been estimated approximately as 25% for SO2, 30% for NO2, and 40% for NO. Using the equation, the method to establish adequate cycles of concentration of a cooling tower water is explained.