Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Papers
Suppression of Ice Formation around a Cooled Tube Using Liquid-Fluidized Bed
(Further Report : Evaluation of Ice Layer as Thermal Resistance)
Kenichi HASHIZUMEYuusuke MIYAMOTOTakahiro MATSUE
Author information
JOURNAL FREE ACCESS

2002 Volume 19 Issue 2 Pages 143-149

Details
Abstract

An experimental study was performed on ice formation around a brine-cooled tube embedded horizontally in a liquid-fluidized bed. It was found that the ice layer thickness evaluated from thermal resistance, equivalent thickness, is thinner than the actual average thickness, and that the ratio of the equivalent to the average thickness depends on a non-dimensional parameter consisted of Biot number and cooling temperature ratio for liquid single-phase flow, and additionally of the Archimedes number for liquid fluidized bed.

Content from these authors
© 2002 Japan Society of Refrigerating and Air Conditioning Engineers
Previous article Next article
feedback
Top