Study on the Partial Load Characteristics of Double-Effect Absorption Systems
Ryuichiro KAWAKAMIToru FUKUCHIYoshio KAITA
Author information
JOURNAL FREE ACCESS

2004 Volume 21 Issue 3 Pages 215-225

Details
Abstract
Simulation analysis was carried out to study the partial load characteristics of three different types of double-effect LiBr-water absorption cycle, namely series flow, parallel flow and reverse flow. A computer program was developed for this study to simulate the behavior of the absorption cycles equipped with flow rate control of absorbent, cooling water and chilling water on partial load. The effects of the flow rate control on the coefficient of performance (COP), the maximum temperature and maximum pressure were studied. The results show that not only flow rate control of absorbent is essential for high COP on the partial load, but also flow rate control of cooling water and chilling water is recommendable to save the power of pumping.