Experimental Study on Efficiency Improvement of R410A Scroll Compressor for Air Conditioner
1st Report :Performance Improvement by Oil-injection into Compression Chamber
Kiyoshi SAWAIAtsushi SAKUDANoboru IIDAAkira HIWATATakashi MORIMOTONoriaki ISHII
Author information
JOURNAL FREE ACCESS

2007 Volume 24 Issue 3 Pages 265-272

Details
Abstract
In scroll compressors, an increase in oil flow rate into thecompression chamber improves sealing effectsand decreases refrigerant leakage. On the other hand, as the oil supplies the heat energy, the suction refrigerantis heated and the volumetric efficiency degreases. In the present study, we made an apparatus which suppliesthe oil into the compression chamber while measuring the mass flow rate, thus investigating the relationshipbetween the oil flow rate and the compressor performance. Experimental results indicated that the presentR410A scroll compressor provided higher performance as the oil flow rate decreased under the rated conditionof the air-conditioner. In addition, based on the experimental results, we discussed that the oil flow in thecapillary installed in the orbiting scroll was considered to be a laminar flow, and the volumetric efficiencywould degrease by the effect of a quarter of the oil heat energy.
Content from these authors
© 2007 Japan Society of Refrigerating and Air Conditioning Engineers