Abstract
Simple expressions to predict actual performance of vapor compression air-conditioners such as room air-conditioners and multi-split type air-conditioners are proposed. Coefficient of performance is expressed in these simple expressions as a function of outdoor temperature, indoor temperature, air-conditioning load rate, air flow rate of indoor unit (in case of room air-conditioners) and difference in height between indoor unit and outdoor unit (in case of multi-split type air-conditioners). Those simple expressions are obtained by neural net work analysis (Rule extraction method from facts, RF5). Actual performance of air-conditioners which are used for training data and teaching data of net work are obtained by numerical simulations developed by the authors. Calculation results of these simple expressions usually agree with experimental values of other researchers. Furthermore, amount of exhaust heat from air-conditioners calculated with these expressions are 10% or lower than traditional approach: calculated with constant value of coefficient of performance.