Abstract
The new ways to control the humidity and the temperature of the room accurately during the dehumidification operation reheated by refrigeration cycle on room air conditioners using R 410A was investigated. The indoor heat exchanger is divided into a condensing part and an evaporating part by a dehumidification valve which is located between these two heat exchangers. The indoor air cooled and dehumidified by the evaporating part is heated by the condensing part. The dehumidification capacity increased according to increasing the compressor rotational speed. And the reheating capacity increased according to decreasing the outdoor fan rotational speed. So the humidity and the temperature of the room was controlled to the setting values exactly by regulating the compressor rotational speed and the outdoor fan rotational speed alternately.