Dehumidification Performance of Humidity Control System with Double Ventilation Sorbent Rotor
Sadao TAKAKIAkihiko HORIBENaoto HARUKIYuki NISHINAHideo INABA
Author information
JOURNAL FREE ACCESS

2009 Volume 26 Issue 4 Pages 489-499

Details
Abstract
The desiccant air-conditioning will be suitable for effective use of the exhaust heat. We have reported high dehumidification efficiency of the proposed system that is composed of a sorbent rotor and a refrigerating cycle. In this study, to improve the sorption efficiency of the rotor, the double ventilation rotor is proposed. After the processing air is dehumidified at the sorption area 1 of the rotor, the air is cooled and has higher relative humidity. And then, the air is blew into the sorption area 2 from the rotor opposite. The double ventilation characteristics on the influence of the division area of the rotor, the flow rate, the recovery temperature, and the temperature of the air cooler were investigated. As a result, the behavior of the double ventilation rotor is clarified and it is found that the quantity of dehumidification of the rotor is greater in the case of 1:1:2 (sorption(1): sorption(2): desorption ) division rate of the rotor than that of 1:1:1.