Measurement of Isobaric Heat Capacity of Gaseous Trans-1,3,3,3-tetrafluoropropene (HFO 1234ze (E) )
Noboru KAGAWAAtsushi MATSUGUCHIKoichi WATANABE
Author information
JOURNAL FREE ACCESS

2011 Volume 28 Issue 1 Pages 71-76

Details
Abstract
The specific isobaric heat capacity (cp) was measured for HFO-1234ze(E) (trans-1,3,3,3-tetrafluoropropene) in the gas phase. HFO-1234ze(E) has a lower GWP value of 6 and is one of new environment-friendly refrigerants. Nineteen measurements for HFO-1234ze(E) were obtained at temperatures from 303 K to 363 K and at pressures from 0.35 MPa to 1.3 MPa. The expanded uncertainty (k=2) of the temperature measurements is estimated to be less 22 mK, and that of the pressure measurements is less 4.4 kPa. The expanded uncertainty for cp is estimated to range from 14 to 21 J.kg-1.K-1.
Content from these authors
© 2011 Japan Society of Refrigerating and Air Conditioning Engineers