Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Papers
Evaluation and Simulation of a Waste Heat Driven Pressurized Solid-Sorption Chiller
Wai Soong LOHKazi Afzalur RAHMANAnutosh CHAKRABORTYBidyut Baran SAHAKim Choon NGWon Gee CHUN
Author information
JOURNAL FREE ACCESS

2011 Volume 28 Issue 3 Pages 299-309

Details
Abstract
This article presents the performance analysis of the pressurized adsorption chiller, which consists mainly of an evaporator, a condenser and two sorption beds. A total of two specimens of adsorbent/adsorbate pairs, namely Maxsorb III/R134a and Maxsorb III/R410a have been investigated. The evaporator temperature is operated between 5 to 12 °C and the condenser temperature is at ambient temperature, i. e. 30 °C. However, these refrigerants enable sub-zero evaporating temperatures. The R134a adsorbate cooling system is operated at lower pressure ranging from 0.35 to 0.77 MPa, and for R410a adsorbate cooling system, the operating pressure is ranging from 1.45 to 1.89 MPa. This shows R134a is more favorable to use due to its lower operating pressures. In current studies, parametric analysis has been carried out to study the effects of adsorption/desorption time and switching time on the system performance in term of cooling capacity and coefficient of performance.
Content from these authors
© 2011 Japan Society of Refrigerating and Air Conditioning Engineers
Previous article Next article
feedback
Top