Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Original Paper
Surface Tension Measurement for a New Low-GWP Refrigerant HFO-1123 by a Differential Capillary Rise Method
Chieko KONDOUYukihiro HIGASHI
Author information
JOURNAL FREE ACCESS

2018 Volume 35 Issue 4 Pages 403-

Details
Abstract

By a differential capillary rise method, the surface tension was measured for a new candidate of low GWP refrigerant HFO-1123. 16 points of surface tension data with a propagated uncertainty of approximately ±0.22 mN m-1 are presented in this paper. Based on the measured data, a Van der Waals type empirical correlation was proposed for HFO-1123: = 61.02 (1-T/Tcrit)1.30 [mN m-1], where Tcrit is a critical temperature of 331.7 K measured by Higashi and Akasaka. This empirical correlation agrees with the measured surface tension data at temperatures from 267 K to 304 K.

Content from these authors
© 2018 Japan Society of Refrigerating and Air Conditioning Engineers
Previous article Next article
feedback
Top