Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Original papers
Correlation Assessment and Temperature Dependence Check ofSurface Tension and Parachor for New Low-GWP Pure Refrigerants
Shun IWASAKIChieko KONDOUYukihiro HIGASHI
Author information
JOURNAL FREE ACCESS

2020 Volume 37 Issue 1 Pages 73-

Details
Abstract

The surface tension was measured for several low-GWP refrigerants, which are grouped in HCFO and HFO, by a differential capillary rise method. The comparison between measured data and calculated value by REFPROP 10.0 were reviewed. The review results suggest that the uncertainty in surface tension calculated by REFROP 10.0 are not negligibly small for R1224yd(Z) and R1336mzz(Z). Based on the measured data and calculated orthobaric densities, “Parachor” was identified for each refrigerant. Among the measured refrigerants, the parachor of only R1336mzz(E) showed obvious temperature dependence, which means there could be an inconsistency between orthobaric densities and surface tension.

Content from these authors
© 2020 Japan Society of Refrigerating and Air Conditioning Engineers