Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Original paper
[title in Japanese]
Daichi SAMPEITetsuaki TAKEDADai MORIYA
Author information
JOURNAL FREE ACCESS

2020 Volume 37 Issue 3 Pages 293-

Details
Abstract

This paper described the experimental results regarding the air conditioning performance of ground source heat pump that use direct expansion method. An underground heat exchanger consists of three parallel copper tubes and one insulated copper tube. The power output of the heat pump was 6.8 kW for cooling and 8.9 kW for heating. The underground heat exchangers were inserted into the three casing pipes made of steel which is 30 m depth. The three-parallel U-shaped underground heat exchanger were connected with the refrigerant circuit in the out-door unit. Experimental results are as follows. During the cooling operation, the average value of the output power, the power consumption, and COP was 1.9 kW, 0.3 kW, and 6.8, respectively. During the heating operation, the average value of the output power, the power consumption, and COP is 3.9 kW, 0.48 kW, and was 8.1, respectively.