Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Papers
Measurements of the Surface Tension for CFC Alternatives
1st Report : Apparatus and Preliminary Experiments for CFC-12, HCFC-22, and CFC-113
Yukihiro HIGASHIMasaaki OKADA
Author information
JOURNAL FREE ACCESS

1992 Volume 9 Issue 2 Pages 181-190

Details
Abstract
On the basis of the differential capillary rise method and the vertical plate method, two kinds of experimental apparatus for measuring the surface tension of CFC alternatives have been constructed. In order to confirm the performance of these experimental apparatus, measurements of the surface tension for CFC-12, HCFC-22 and CFC-113 have been made in the range of temperatures between 273 and 343 K. The uncertainty of temperature measurement for the differential capillary rise method is estimated within ±20mK, whereas that for the vertical plate method is estimated within ±30mK. As the results of the comparisons between the present work and other investigations, the uncertainties of these measurements are estimated within ±0.1mN/m with the apparatus for the differential capillary rise method and within ±0.2mN/m with that for the vertical plate method.
Content from these authors
© 1992 Japan Society of Refrigerating and Air Conditioning Engineers