Simplified COP Correlations for Industrial Heat Pumps using the 2nd Law Efficiency
Takenobu KAIDAShoji MORI
Author information
JOURNAL OPEN ACCESS Advance online publication

Article ID: 25-03

Details
Abstract

This study aims to develop a unified and simple method for estimating the energy performance of a wide variety of industrial heat pumps. First, energy performance data on industrial heat pumps available in the Japanese market are collected and analyzed. Then, based on the regression analysis, two types of correlations between Lorenz efficiency, which is the second law efficiency, and logarithmic mean temperature lift are developed. The first type correlation can estimate the average COP (coefficient of performance) of industrial heat pumps with single stage cycles with an accuracy of approximately within ±10%. On the other hand, the second type correlation represents the highest performance of existing technologies including two stage cycles and cascade cycles. Both correlations can be calculated by inputting 6 parameters: heat source medium, heat sink medium, heat source inlet and outlet temperatures, and heat sink inlet and outlet temperatures.

Content from these authors
© Japan Society of Refrigerating and Air Conditioning Engineers

この記事はクリエイティブ・コモンズ [表示 - 非営利 - 改変禁止 4.0 国際]ライセンスの下に提供されています。
https://creativecommons.org/licenses/by-nc-nd/4.0/deed.ja