EXAMINATION ABOUT THE EFFECTS OF OPENING OF THE MAGNETIC SHIELD PLATE AROUND THE ELECTRIC POWER LINE
Naoya KUBOKazunori NISHIMURANobuyoshi KIYOTA
Author information
JOURNAL FREE ACCESS

2015 Volume 80 Issue 716 Pages 897-903

Details
Abstract
 Magnetic shielding in a building requires a method for thermal radiation. Therefore, magnetic shielding effectiveness when magnetic material of perforated metal surrounds four aspects of electric power line circumference was examined by both of a physical experiment with practical size of three-phase electric power line and a simulation experiment with finite element method. In the results, high magnetic shielding effectiveness was observed under a condition of large opening ratio, however the condition can easily lead magnetic saturation at relatively low AC current. In addition, a difference of opening alignments made a small difference which can be ignored.