Journal of Environmental Engineering (Transactions of AIJ)
Online ISSN : 1881-817X
Print ISSN : 1348-0685
ISSN-L : 1348-0685
EVALUATION OF SPATIAL AND TEMPORAL DISTRIBUTION OF PMV WITH CONSIDERING CONTROL AND PERFORMANCE CHANGE OF HVAC SYSTEM
Thermal environment evaluation in office over cooling period with direct cooling system of internal heat gain Part 2
Li WANGShinsuke KATOWeirong ZHANGHyokeun HWANGTaiki SATOKentaro SEKINE
Author information
JOURNAL FREE ACCESS

2017 Volume 82 Issue 733 Pages 237-247

Details
Abstract

 In previous study, indoor thermal environment in occupied zone of direct cooling system of internal heat gain was evaluated by taking the space distribution and time change into consideration. A method that is similar to quasi-coupling simulation of contribution ratio of indoor climate (CRI) and energy-network model was used to realize the calculation of predicted mean vote (PMV). However, the control and performance change of the HVAC system were not involved in previous evaluation, which cannot be ignored. In this study, the control and performance of the four components of the HVAC system, liquid cooling - heat recovery unit (HRU), active chilled beam (ACB), radiation partition (RP) and dry fan coil unit (DFCU) are modeled. Then, with considering control and performance change of the HVAC system, a basic case study is conducted to evaluate the spatial and temporal PMV distribution of occupants. Results showed that the indoor thermal comfort was affected obviously by the operation-controlled strategy of water distribution system of ACB. As well as previous results, the differences of PMV value were smaller and the comfortability rates were higher than those by conventional system.

Content from these authors
© 2017 Architectural Institute of Japan
Previous article Next article
feedback
Top