2026 Volume 91 Issue 845 Pages 797-803
This study evaluates ATP bioluminescence as a screening indicator for deterioration of ceiling gypsum boards affected by water leakage. Two field investigations of in-service ceiling boards showed that stained areas exhibited higher ATP values and lower maximum load in three-point bending than adjacent sound areas. Ring-shaped stains showed non-uniform ATP values within the ring, and amplicon sequencing suggested bacterial community differences between the rim and inner region. In a leakage exposure test, ATP values aligned with maximum load decreases more clearly than appearance-based brightness differences. Overall, ATP bioluminescence can potentially support non-destructive ceiling diagnosis by identifying areas suspected of deterioration.
Code of Ethics
Ethical standards of the publisher (‘Ethical Standards Concerning the Peer Review for the Presentation of Architectural Transactions and Works’)