THE EXPERIMENTAL STUDY ON THE ROOF VENTILATOR
CHITOSHI KATSUTATAKESHI SEKINE
Author information
JOURNAL FREE ACCESS

1963 Volume 88 Pages 12-21

Details
Abstract
1. In order to calculate the quantity of natural ventilation caused by the ventilator which equipped in construction (see Fig. 1), the following equation should be used as practical. [table] where [table] and [numerical formula] where P_0; wind pressur on vetilator head, kg/m^2 C_<0s>; coefficient of static wind pressure at ventilator head C_<0d>; coefficient of dynamic wind pressure on ventirator head α; wind velocity radio [numerical formula]; pressure loss of vetilator entrance & elbow, kg/m^2 [numerical formula]; pressure loss of straight part of ventilator, kg/m^2 ζ_v; loss coefficient of ventilator head v; wind velocity in ventlator P_i, C_i, ζ_i,V_i; see another report. 2. As for the loss coefficient of ventilator head, following equation is explained. [table] and [table] where P_s: static pressure at ventilator neck, kg/m^2 P_0: total wind pressure at ventilator neck when air move in ventilator is stopped, kg/m^2 V_v: wind velocity near the ventilator head, m/s θ_x: vertical wind direction at ventilator head. The relation between the v/V, θ_x and ζ_v about many kinds ventilator which show Fig. 2 are ilustlated in Fig. 4〜13.