RESULTS OF LONG-TERM MEASUREMENT RELATED TO PRESTRESSING FORCE IN PERMANENT GROUND ANCHOR
Toshihiro MORI
Author information
JOURNAL FREE ACCESS

2010 Volume 16 Issue 33 Pages 489-492

Details
Abstract
Measurement of prestressing force in permanent ground anchors, which was used in order to prevent the building from floating by the lift of ground water or in case of an earthquake, was carried out over the long period of time. When the prestressing force of 60 years after was presumed based on the measurement result, the effective prestressing rate was set from 0.84 to 0.95, and was around 0.9. As a result of comparing the calculated value and measurement value, it was found that the adoption value at the time of a design was appropriate.