AIJ Journal of Technology and Design
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
Fire Safety
A STUDY ON SMOKE BEHAVIOR IN A COMPARTMENT WITH SPRINKLER SYSTEM ACTIVATION
−Experiment by full scale compartment−
Mitsuru OTAYoshifumi OHMIYAKen MATSUYAMAMasaki NOAKIJun-ichi YAMAGUCHI
Author information
JOURNAL FREE ACCESS

2013 Volume 19 Issue 41 Pages 169-174

Details
Abstract
Sprinklers are the most popular and reliable system for controlling fires. But the studies on smoke behavior with sprinkler activation are hardly studied. In This paper, smoke behavior with sprinkler activation was studied. Experiments were conducted on a full scale and the following results were obtained; the temperature of the upper layer was decreased, and the lower layer was raised by effect of water spray. As amount of water increased, CO2 density of the upper layer was decreased and lower layer was increased.
Content from these authors
© 2013 Architectural Institute of Japan
Previous article Next article
feedback
Top